Power Systems is 8-12 questions on the FE Electrical exam, the second-largest electrical area. It is the most formula-driven part of the paper: the power triangle, the three-phase relations, the ideal transformer and the machine equations answer nearly everything.
The traps are conventions rather than concepts: line versus phase quantities, the sign of reactive power, which angle goes into the power factor, and whether a percentage refers to regulation or efficiency.
Exam weight: NCEES lists Power Systems at 8-12 questions of the 110-question FE Electrical and Computer exam. Work each problem below on paper first, then reveal the worked solution — reading a solution you have not attempted builds recognition, not recall.
What NCEES Tests in Power Systems
The specification lists power theory (power factor, single and three phase, voltage regulation), transmission and distribution (real and reactive losses, efficiency, voltage drop, delta and wye connections), transformers (single-phase and three-phase connections, reflected impedance) and motors and generators (synchronous, induction, dc).
The specification lists power theory (power factor, single- and three-phase, voltage regulation), transmission and distribution (real and reactive losses, efficiency, voltage drop, delta and wye connections), transformers (single- and three-phase connections, reflected impedance) and motors and generators (synchronous, induction, DC).
Expect the complex power of a load from its voltage and current, the capacitor needed to correct a power factor, the line current and total power of a balanced wye or delta load, the voltage regulation of a line or transformer, the reflected impedance through a transformer, the synchronous speed and slip of an induction motor, and the back EMF or torque of a DC machine.
5 Free Power Systems Practice Problems
Each power systems problem below comes from the FEExamClick FE Electrical question bank, with worked solutions that cite the FE Reference Handbook page, and matches the style, difficulty and format of the real exam. Attempt each one under a three-minute limit — roughly the pace the exam demands.
Problem 1 — A. Power theory (power factor, single and three phase, voltage regulation)
A purely resistive load draws 10 A from a 120 V rms source. What reactive power does the load absorb?
Answer: A) \(0\text{ var}\)
The Handbook defines reactive power as \(Q = V_{rms} I_{rms}\sin\theta\) with \(\theta\) the angle from the voltage to the current. In a resistor the current is in phase with the voltage, so \(\theta = 0\) and its sine is zero:
$$Q = 120 \times 10 \times \sin 0^\circ = 0\text{ var}$$
All of the \(1200\) VA drawn is real power, \(P = 120 \times 10 \times \cos 0^\circ = 1200\) W, which the Handbook also writes for resistors as \(P = I^2 R = V^2/R\) with \(R = 12\ \Omega\). Reactive power is the energy that sloshes back and forth between the source and the magnetic or electric field of a reactive element; a resistor stores no energy, so it returns none, and its power factor is unity. Only inductors and capacitors carry reactive power, positive for the inductor and negative for the capacitor.
1200 var is \(VI\), the whole apparent power assigned to \(Q\) as if the load were a pure reactance with \(\theta = 90^\circ\).
600 var is half of \(VI\), as if the angle were \(30^\circ\).
1697 var is \(VI\) computed with the peak voltage, \(120\sqrt{2} \times 10\); the Handbook's formulas use rms values, and in any case a resistor has no reactive power at all.
Problem 2 — B. Transmission and distribution (real and reactive losses, efficiency, voltage drop, delta and wye connections)
The figure shows a single-phase load fed through a transmission line. What is the magnitude of the receiving-end voltage?
Answer: D) 2363 V
Handbook: FE Reference Handbook 10.6, Electrical and Computer Engineering:
• Kirchhoff's Laws, p. 363 (PDF viewer: page 368) — the sum of voltage rises equals the sum of voltage drops around a closed path.
• Phasor Transforms of Sinusoids, p. 366 (PDF viewer: page 371) — \(\mathbf{Z} = \mathbf{V}/\mathbf{I} = R + jX\).
Around this loop, KVL in phasor form gives
$$\mathbf{V}_R = \mathbf{V}_s - \mathbf{I}\,\mathbf{Z}_{line}$$
Step 1 – Put the line impedance in polar form.
$$\mathbf{Z}_{line} = 0.5 + j1.0 = 1.118\angle 63.43^\circ \;\Omega$$
Step 2 – The drop along the line. Magnitudes multiply, angles add:
$$\mathbf{I}\,\mathbf{Z}_{line} = (40\angle{-30^\circ})(1.118\angle 63.43^\circ) = 44.72\angle 33.43^\circ \text{ V}$$
$$= 44.72\cos 33.43^\circ + j\,44.72\sin 33.43^\circ = 37.32 + j24.64 \text{ V}$$
Step 3 – Subtract as phasors, not as numbers. This is the step the whole problem is built around. \(\mathbf{V}_s\) lies along the real axis, so
$$\mathbf{V}_R = 2400 - (37.32 + j24.64) = 2362.68 - j24.64 \text{ V}$$
$$|\mathbf{V}_R| = \sqrt{2362.68^2 + 24.64^2} = 2363 \text{ V}$$
Answer: (D).
Why the 24.6 V of quadrature drop is almost invisible. The imaginary part of the drop sits at right angles to a 2400 V phasor, so it barely changes the length: it contributes \(24.64^2/(2 \times 2363) \approx 0.13\) V. That is not a coincidence of these numbers, it is the general reason the field approximation \(V_R \approx V_s - \text{Re}(\mathbf{I}\mathbf{Z})\) works on distribution lines. The in-phase part of the drop is what moves the magnitude.
Reading the sign check off the current. \(\mathbf{I}\) lags \(\mathbf{V}_s\) by 30°, so the load is inductive and the line is delivering both real and reactive power to it. For a lagging load the receiving end is always below the sending end, which settles two of the four options before any arithmetic.
Step 4 – Eliminate the distractors:
(C) 2400 V is the sending-end voltage copied out unchanged — the line drawn with an impedance in it, and then the impedance ignored. It is the answer only for a lossless line carrying no current.
(A) 2380 V is \(2400 - |I|R = 2400 - 40(0.5)\): the resistive part of the line kept and the reactance thrown away. That is the same 20 V a dc calculation would give, and it misses that the reactance is twice the resistance here.
(B) 2437 V is \(|\mathbf{V}_s + \mathbf{I}\mathbf{Z}_{line}|\) — the drop added instead of subtracted, which is the formula for going the other way, from a known receiving end back to the sending end. The figure labels which end the 2400 V belongs to, and a passive lagging load cannot raise the voltage above the source.
Problem 3 — D. Motors and generators (synchronous, induction, dc)
A three-phase synchronous generator is rated 500 kVA at 480 V (line-to-line) and has a synchronous reactance of \(1.2\ \Omega\) per phase. What is its rated line current?
Answer: B) \(601\text{ A}\)
The rated current is the current at rated apparent power and rated voltage, from the Handbook's balanced three-phase \(|S| = \sqrt{3} V_L I_L\):
$$I_L = \dfrac{S}{\sqrt{3}\,V_L} = \dfrac{500{,}000}{\sqrt{3} \times 480} = 601\text{ A}$$
The synchronous reactance plays no part in the rating; it would enter only in finding the internal voltage \(E_a\) needed to hold 480 V at this current, which by the Handbook's synchronous machine model is \(V_{an} + jX_s I_a\) with \(V_{an} = 277\) V, giving \(|E_a| = \sqrt{277^2 + (1.2 \times 601)^2} = 773\) V per phase at unity power factor. The rated current is a winding limit set by heating and holds whatever the power factor, which is why generators, like transformers, are rated in kVA rather than kW.
1042 A is \(S/V_L\) with the \(\sqrt{3}\) left out, the single-phase formula.
347 A divides by \(3 V_L\), using 3 where \(\sqrt{3}\) belongs with line quantities.
1804 A multiplies by \(\sqrt{3}\) instead of dividing.
Problem 4 — B. Transmission and distribution (real and reactive losses, efficiency, voltage drop, delta and wye connections)
A three-phase, 12.47 kV (line-to-line) line has a resistance of \(1\ \Omega\) and a reactance of \(3\ \Omega\) per phase and delivers 3 MW at a power factor of 0.8 lagging with 12.47 kV at the receiving end. Using the approximation \(\Delta V \approx I(R\cos\theta + X\sin\theta)\) for the per-phase drop, and taking the no-load receiving-end voltage as the sending-end voltage, what is most nearly the percent voltage regulation of the line?
Answer: B) \(6.3\%\)
The line current from the Handbook's three-phase power:
$$I_L = \dfrac{3 \times 10^6}{\sqrt{3} \times 12{,}470 \times 0.8} = 173.6\text{ A}$$
With \(\cos\theta = 0.8\) and \(\sin\theta = 0.6\), the per-phase drop is
$$\Delta V \approx 173.6\,(1 \times 0.8 + 3 \times 0.6) = 173.6 \times 2.6 = 451\text{ V}$$
The receiving-end phase voltage at full load is \(12{,}470/\sqrt{3} = 7200\) V, and the sending-end phase voltage, which is what the receiving end would rise to at no load, is about \(7200 + 451 = 7651\) V. The Handbook's regulation is the rise referred to the full-load voltage:
$$\%\text{Regulation} = \dfrac{V_{NL} - V_{FL}}{V_{FL}} \times 100 = \dfrac{451}{7200} \times 100 = 6.3\%$$
The same figure results from line-to-line quantities, since both the drop and the voltage scale by \(\sqrt{3}\) together. The regulation is high because the load is lagging and the line reactive: the \(X\sin\theta\) term contributes 1.8 of the 2.6 V per ampere.
3.6% divides the per-phase drop by the line-to-line voltage, mixing the two bases.
7.6% uses \(I|Z| = 173.6 \times 3.16 = 549\) V, the full impedance drop with no regard to its angle.
10.9% multiplies the per-phase drop by \(\sqrt{3}\) before dividing by the per-phase voltage.
Problem 5 — C. Transformers (single-phase and three-phase connections, reflected impedance)
The figure shows a transformer bank running with only two of its three units. What is the maximum three-phase apparent power the bank can deliver?
Answer: A) 173.2 kVA
Handbook: FE Reference Handbook 10.6, Electrical and Computer Engineering → Three-Phase Transformer Connection Diagrams, p. 370 (PDF viewer: page 376), which draws the delta-delta connection this bank came from. The words open delta and V-V appear nowhere in the Handbook, and there is no capacity formula for it. What follows uses only the delta relations from p. 368, \(V_L = V_P\) and \(I_L = \sqrt{3}I_P\), and the standard \(|S_{3\phi}| = \sqrt{3}V_LI_L\).
Step 1 – What limits the bank now. In a full delta each winding carries \(I_L/\sqrt{3}\), because the line current splits between two windings at every vertex. With one transformer gone there is no splitting left: follow conductor \(a\) in the figure and it lands on a single winding, so
$$I_{winding} = I_L$$
The transformers are unchanged, so the winding current is still capped at its rated value:
$$I_{winding,rated} = \frac{S_{1\phi}}{V_{winding}} = \frac{100{,}000}{240} = 417 \text{ A}$$
and that is now the ceiling on the line current.
Step 2 – Turn that line current into three-phase capacity. A delta keeps \(V_L = V_P = 240\) V, so
$$|S_{3\phi}| = \sqrt{3}\,V_L I_L = \sqrt{3}\,V_{winding}I_{winding,rated} = \sqrt{3}\,S_{1\phi}$$
$$|S_{3\phi}| = \sqrt{3} \times 100 = 173.2 \text{ kVA}$$
Answer: (A).
Two numbers worth carrying, and they answer different questions.
$$\frac{173.2}{300} = 57.7\% = \frac{1}{\sqrt{3}} \qquad\qquad \frac{173.2}{200} = 86.6\% = \frac{\sqrt{3}}{2}$$
The first is what the bank can still do compared with all three transformers in service — the answer to "how much load must I shed after a unit fails?". The second is how hard the two survivors are working: each is loaded to 86.6% of its own rating, not 100%, because their currents are 60° out of phase with the voltages across them rather than at the angle the load asks for. Both are true, and the 57.7% is the one this question is about.
Why anyone builds this deliberately. Open delta still produces three-phase voltages from two transformers, so a utility can serve a small three-phase load with two units and add the third when the load grows — or keep a customer running after one unit fails. What it costs is that 13.4% of the installed transformer capacity is unusable.
Step 3 – Eliminate the distractors:
(C) 200 kVA is \(2 \times 100\), the two remaining transformers added arithmetically. That is the installed capacity, not the deliverable capacity: it would require each winding to carry rated current in phase with rated voltage, and in a V-V bank the phase relationship makes that impossible.
(B) 300 kVA is the full three-transformer bank, \(3 \times 100\) — the rating before the failure. The figure shows only two transformers.
(D) 100 kVA is one transformer's rating. Two units are in service and both are carrying load; the answer has to exceed a single unit.
Using the FE Reference Handbook for Power Systems
The Handbook gives AC power, complex power and balanced three-phase systems on p. 368, ideal transformers and the turns ratio on p. 369, three-phase transformer connections and rotating machines on p. 370, AC, synchronous and induction machines on p. 371, DC machines on p. 372 and voltage regulation on p. 373. The per-unit system, the approximate line-drop formula and the air-gap power split are not written in the Handbook, so questions that need them state the relation.
Four Mistakes That Cost Points
- Using the line angle in the power factor. The power factor angle is the angle of the phase impedance, the angle between phase voltage and phase current. The 30-degree shift between line and phase quantities is not part of it.
- Mixing line and phase values in the three-phase power formula. Total power is root three times line voltage times line current times the power factor, or three times the phase values. Using line voltage with phase current is off by root three.
- Reflecting an impedance with the ratio instead of its square. An impedance on the secondary appears at the primary multiplied by the square of the turns ratio. Using the ratio itself is the standard distractor.
- Dropping the neutral-point rule for delta loads. A delta load has no neutral, its phase voltage equals the line voltage, and its line current is root three times the phase current. Treating it as a wye reverses every relation.
Frequently Asked Questions
How many power systems questions are on the FE Electrical exam?
NCEES specifies 8-12 questions out of 110, the second-largest electrical knowledge area.
What is the quickest way to handle a balanced three-phase problem?
Convert every delta to its wye equivalent, analyze a single phase with the line-to-neutral voltage, then multiply the per-phase power by three. It avoids every line-versus-phase trap.
How is power factor correction calculated?
The capacitor must supply the difference in reactive power: the real power times the difference between the tangents of the old and new power-factor angles. The capacitance follows from that reactive power, the voltage and the frequency.
Which machine formulas matter most?
Synchronous speed from frequency and poles, slip, the split of air-gap power between rotor loss and mechanical power for induction motors, the generated voltage and torque of a DC machine, and the ideal transformer relations.
Keep Going
These topics feed into each other on the exam:
- FE Electrical Circuit Analysis practice problems — 11-17 questions on the exam
- FE Electrical Electromagnetics practice problems — 4-6 questions on the exam
- FE Electrical Electronics practice problems — 7-11 questions on the exam
Done with power systems? Browse every knowledge area from the free FE Electrical practice problem hub, see what the full bank covers on the FE Electrical exam prep page, or plan your schedule with the FE study timeline. Or test yourself against the clock with the free FE Electrical practice exam: 20 timed questions in the CBT format.